Table 8

Recommendations relative to ventilation37

SourcesRecommendation
Kwok241500 feet3/min during the operation of the resurfacer 5000–7500 feet3/min all of the time
Oatman and Zetterlund311700–2500 feet3/min for arenas of 300000
12000–17500 feet3/min for arenas of 2000000
Davis and Drenchen1950000 feet3/min during the operation of the resurfacer
Anderson1310000 feet3/min when using a propane resurfacer
15000 feet3/min when using a gas resurfacer
American Society of Heating Refrigerating and Air-conditioning Engineers710–15 feet3/min per person
Ontario Recreation Facilities Association57300 feet3/min for each volume3 of the resurfacer used